Product details
DATE ELECTRICE GENERALE
| Putere standby (ESP = Emergency standby power) | kVA | 2250 | ||
| kW | 1800 | |||
| Putere prime (PRP = Prime Power) | kVA | 2025 | ||
| kW | 1512 | |||
| Factor de putere | cos ɸ | 0.8 | ||
| Tensiune | V | 400 VAC | ||
| Frecventa | Hz | 50 |
DATE CONSTRUCTIVE
| Structura | - | carcasa insonorizata | ||
| Nivel de zgomot ( la 7 m distanta) | dB | 70 | ||
| Gabarit | Lungime ( L ) | mm | 9000 | |
| Latime ( l ) | mm | 2450 | ||
| Inaltime ( h ) | mm | 3500 | ||
| Greutate | kg | 18000 | ||
| Material sasiu | - | otel | ||
| Material carcasa ( tabla ) | - | otel | ||
| Acoperire | - | vopsea | ||
| Rezervor integrat de combustibil | - | da | ||
| Capacitate rezervor integrat in sasiu | litri | 3000 | ||
| Usi laterale (pentru acces interior usor) | - | da | ||
| Balamale din otel inox | - | - |
MOTOR
| Producator | - | YUCHAI | ||
| Model | - | YC12VC2700-D31 | ||
| Putere mecanica | kWm | 1985 | ||
| Tip motor | - | Diesel | ||
| Ciclu de functionare | - | 4 timpi | ||
| Aspiratie | - | turbo intercooler | ||
| Combustibil | - | motorina | ||
| Nr. cilindri | - | V12 | ||
| Cilindree | litri | 79.17 | ||
| Alezaj | mm | 200 | ||
| Cursa | mm | 210 | ||
| Rata de compresie | - | 13,5:1 | ||
| Racire | - | cu apa | ||
| Capacitate totala lichid racire | 676 l | |||
| Regulator de turatie | - | Electronic unit pump | ||
| Viteza de rotatie | rpm | 1500 | ||
| Capacitate baie ulei (max.) | litri | 310 | ||
| Redresor de baterii | - | Da | ||
| Numar de baterii | - | 2 | ||
| Tensiune baterie | V | 24 (2 x 12 V) | ||
| Rezistenta preincalzire antigel (preheater) | - | Da |
ALTERNATOR
| Producator | - | STAMFORD | |
| Model | - | S7L1D-H | |
| Putere (standby) | kVA | 2250 | |
| Factor de putere | - | 0.8 | |
| Frecventa | Hz | 50 | |
| Fara perii | - | da | |
| Plaja de reglare a tensiunii | % | ±1 | |
| Izolatie | - | Clasa H | |
| Protectie | - | IP 23 | |
| Numar de rulmenti | - | 1 | |
| Grup electrogen MARRO MYH 2250 I Panoul de control |
PANOUL DE CONTROL
| Producator | - | DEEP SEA | |
| Model | - | DSE 7320/7420 | |
| Afisaj | - | LCD | |
| DATE GENERALE • Masuratori reale ale parametrilor • Display synchroscop • Baterie pentru ceasul intern • Posibilitate de a simula (pentru a invata) pornirile • Programare saptamanala pentru operare • Suport in mai multe limbi • Jurnal cu 400 evenimente (inclusiv timp si parametri) • Free PC software (USB-Modbus-IP Connected) • Central monitoring software FUNCTII • Unitate AMF cu transfer neintrerupt de sarcina • Unitate AAR cu transfer neintrerupt de sarcina • Controller pornire automata • Controller pornire manuala • Controller motor • Unitate de comanada diplay & unitate de control COMMUNICATII • Ethernet • GSM-GPRS(optional) • Intern: modem GPRS (optional) • Monitorizare web • Web programming • GSM-SMS • e -mail • Software de conectare la calculator (gratuit) • Modbus RS-485 • Modbus over IP • SNMP • USB Host(optional) • USB Device • RS-485 • RS-232 (optional) • Micro SD card slot (optional) • J1939-CANBUS |
CONSUM -PRP
| 100 % sarcina . | litri / ora | 441.9 | |
| 75 % sarcina | litri/ ora | 342.6 | |
| 50 % sarcina | litri/ ora | 236 |
CERTIFICARI
| Echipamentul este produs in sistem certificat ISO 9001, ISO 14001 si CE. | |||
| NOTA: Informatiile si imaginile prezentate in acest document sunt cu titlu informativ si pot suferi modificari fara notificari prealabile | |||
| Conditiile ambientale de functionare de referinta sunt cele mentionate in normativul ISO 8528-1:2018: 1000 mbar, 25 ºC, umiditate relativa 30%. Prime Power (PRP) - In conformitate cu ISO 8528-1:2018, Prime power (sau puterea continua/de productie) este puterea maxima pe care un generator electric este capabil sa o produca in timp ce furnizeaza o sarcina electrica variabila. Generatorul electric este functional un numar nelimitat de ore / an in conditii cunoascute, cu conditia ca intervalele si procedurile de mentenanta prescrise de producator sa fie respectate. Emergency Standby Power (ESP) - In conformitate cu ISO 8528-1:2018, Emergency standby power (sau puterea in regim de avarie/urgenta, standby) este puterea maxima disponibila furnizata de un generator electric in timpul unei perioade cu variatii de putere electrica, putere pe care generatorul electric este capabil sa o furnizeze in eventualitatea unei caderi a retelei sau in conditii de test, pentru cel mult 500 ore / an. Este obligatorie respectarea intervalelor si procedurilor de mentenanta prescrise de producator |